HSW.JPG Rosette with HSW.JPG

RD060 Horizontal Sidewall Standard Response Sprinklers

  • FM Approved Logo Mid Grey 300.jpg
  • UL Logo Mid Grey.jpg
  • LPCB Logo Mid grey 566d-01.jpg
  • VdS Logo mid grey 2.jpg
  • CE Logo Mid Grey 144.jpg
  • UKCA black Mid Gray.jpg
  • gost logo 300.jpg
  • MiB_Logo_Vertical_Colour.jpg
K factor 80 (5.6)
Standard Orifice Size 15mm (½”)
Standard Thread Size ½” NPT
Response Standard Response
Bulb 5mm
Maximum Working Pressure 12.1 bar (175 psi)
Finish Brass, chrome and white paint finish. Special RAL colours available on request
Approvals FM, UL, LPCB, VdS, CE, UKCA, Gost

Rapidrop RD060/RD061 HSW are Standard/Quick Response frangible glass bulb automatic sprinklers. They are CE Marked, LPCB, VdS, FM approved, UL listed, standard orifice fire sprinklers for installation in fire sprinkler systems. In a fire condition the heat causes the fluid in the glass bulb to expand which shatters the glass and releases the spring seal assembly. Water flows from the orifice onto the sprinkler deflector which diffuses the water into a uniform spray pattern in order to control the fire.
Sidewall Sprinklers are designed for installation along a wall or side of a beam beneath a smooth ceiling.

Specifications

K factor K80 (K5.6)
Standard Office Size 15mm (½”)
Thread Size ½”NPT
R½” - ½”BSPT available on special order
Max. Working Pressure 12 bar (175 psi)
Min. Operating Pressure 0.5 bar (7 psi)
Factory Pressure Test 100% at 34 bar (500 psi)
Weight  60.6 grams (2.14 oz.)
Fitted with Bulb Protector Remove after installing sprinkler

 

Operating Temperatures

Nominal Operating Temperature Bulb Colour
57ºC (135ºF) Orange
68ºC (155ºF) Red
79ºC (175ºF) Yellow
93ºC (200ºF) Green
141ºC (286ºF) Blue

 

RD060 Design Coverage 

For sprinkler coverage area and placement refer to NFPA 13,  EN12845 or CEA4001 standards or other Installation rules for automatic sprinkler systems as required by the authority having jurisdiction. The following details are provided for information only.

RD060, RD061 Horizontal Side Wall Fire Sprinkler Head Dimensions

RD060, RD061 Horizontal Side Wall Fire Sprinkler Head Spray Patterns

RD060, RD061 Horizontal Side Wall Fire Sprinkler Head Spray Patterns

 

Rapidrop K80 (K5.6) Sprinkler Flow Characteristics

RD060, RD061 Minimum Operating Pressure, Horizontal Side Wall Fire Sprinkler Head