RD060 Horizontal Sidewall Standard Response Sprinklers
K factor | 80 (5.6) |
---|---|
Standard Orifice Size | 15mm (½”) |
Standard Thread Size | ½” NPT |
Response | Standard Response |
Bulb | 5mm |
Maximum Working Pressure | 12.1 bar (175 psi) |
Finish | Brass, chrome and white paint finish. Special RAL colours available on request |
Approvals | FM, UL, LPCB, VdS, CE, UKCA, Gost |
Rapidrop RD060/RD061 HSW are Standard/Quick Response frangible glass bulb automatic sprinklers. They are CE Marked, LPCB, VdS, FM approved, UL listed, standard orifice fire sprinklers for installation in fire sprinkler systems. In a fire condition the heat causes the fluid in the glass bulb to expand which shatters the glass and releases the spring seal assembly. Water flows from the orifice onto the sprinkler deflector which diffuses the water into a uniform spray pattern in order to control the fire.
Sidewall Sprinklers are designed for installation along a wall or side of a beam beneath a smooth ceiling.
Specifications
K factor | K80 (K5.6) |
Standard Office Size | 15mm (½”) |
Thread Size | ½”NPT R½” - ½”BSPT available on special order |
Max. Working Pressure | 12 bar (175 psi) |
Min. Operating Pressure | 0.5 bar (7 psi) |
Factory Pressure Test | 100% at 34 bar (500 psi) |
Weight | 60.6 grams (2.14 oz.) |
Fitted with Bulb Protector | Remove after installing sprinkler |
Operating Temperatures
Nominal Operating Temperature | Bulb Colour |
57ºC (135ºF) | Orange |
68ºC (155ºF) | Red |
79ºC (175ºF) | Yellow |
93ºC (200ºF) | Green |
141ºC (286ºF) | Blue |
RD060 Design Coverage
For sprinkler coverage area and placement refer to NFPA 13, EN12845 or CEA4001 standards or other Installation rules for automatic sprinkler systems as required by the authority having jurisdiction. The following details are provided for information only.
Rapidrop K80 (K5.6) Sprinkler Flow Characteristics
- Data Sheet 4.53 C [EN]
- Data Sheet 4.53 D [PL]
- Data Sheet 4.53 A [SR]
- RD060 Sprinklers - FM Certificate
- RD060 Sprinklers - UL Certificate
- RD060 Sprinklers - ULc Certificate
- RD060 Sprinklers - LPCB Certificate
- RD060 Sprinklers - VdS Certificate
- RD060 Sprinklers - CE Certificate
- RD060 and RD061- UKCA Certificate